Posts Tagged Clock

Baumer Thalheim Encoder ATD 4S A B4 Y10

Baumer Thalheim Encoder ATD 4S A B4 Y10

Baumer Thalheim Encoder ATD 4S A B4 Y10

Baumer Thalheim Encoder ATD 4S A B4 Y10

Voltage supply: 10…30 VDC
Reverse polarity protection: Yes
Consumption w/o load: ≤70 mA (24 VDC)
Interface: SSI
Function: Multiturn
Steps per turn: ≤32768 / 15 bit
Number of turns: ≤16777216 / 24 bit
Incremental output: 4096 pulses A, B + inv. (Optional), 4096 pulses A, B, sine 1 Vpp. (optional)
Offset sine/cosine amplitude: ≤1 Vpp at Z0 (120 Ohm)
Overlaying constant share: ≤2.5 V
Sensing method: Optical
Code: Gray or binary
Code sequence: CW: ascending values with clockwise sense of rotation (looking at mounting surface), CW/CCW coded and programmable by connection
Inputs: SSI clock, Reset input
Output circuit: SSI data: linedriver RS485, Diagnostic output: error
Interference immunity: DIN EN 61000-6-2
Emitted interference: DIN EN 55011
Programming interface: RS485
Programmable parameters: Steps per revolution, Total resolution, Rotational direction CW/CCW

 

 

 

 

 

, , , , , , , , , , , , , , , , , , , , , ,